Telecom Design Guide
 
Click Here To Visit Our Sponsor
Click Here To Visit Our Sponsor

Home     Search     Ask the Expert     Newsletter      Links      Site Map      Contact Us

Product Design      EMC Guide      National Variants     Telecoms Design Guide      FAQ

Click here to order standards from

Advertise with i-Spec          Contact  advert@i-spec.com for details


 

Interface Types

Interface type

Subjected to overvoltages (i.e. leaves the building)

Not subjected to overvoltage (i.e. does not leave the building)

Defined in the standard as

Requirements

E1, T1

X

 

TNV1

Requirements

E1, T1

 

X

SELV

No requirements

Analog Telephone line, modem (POTS)

X

 

TNV3

Requirements

Analog Telephone line, modem (POTS)

 

X

TNV2

Requirements

ISDN S

 

X

SELV

No requirements

ISDN U

X

 

TNV1

Requirements

Ethernet

10base-T

100Base-T

 

X

SELV

No requirements

xDSL lines - Line Voltage above 120V dc

 

X

RFT

Not covered by IEC60950

xDSL lines - Line Voltage up to 120V dc

X

 

TNV3

Requirements

 


E1,T1 (TNV1)

All PRI interfaces, which connect to the Central Office, should comply with the TNV1 insulation requirements.

DESIGN REQUIREMENTS

DESIGN GUIDE

Accessibility

No access to E1,T1 connectors with the TEST PROBE 

No access to E1,T1 circuits with TEST FINGER

Voltage limitations

Do not exceed SELV requirements (42.4Vp, 60Vdc)

Physical spacing 

No requirements

Electrical separation

E1,T1 circuits Shall be separated from SELV  circuits by  1000Vac or 1414Vdc (sample diagram 1) (See Note)

E1,T1 circuits Shall be separated from Mains  circuits by  2000Vac or 2828Vdc for US (sample diagram 2) (See Note)

E1,T1 circuits Shall be separated from Mains  circuits by  3000Vac or 4242Vdc for Europe (sample diagram 2) (See Note)

UL over-voltage

Need to perform tests for overvoltage from line crossing

Protection of Telecommunication wiring from Over-heating

If E1, T1 provides remote power feeding (DC phantom voltages) the following apply:

  • Connecting wires and cables AWG is clearly defined in installation instructions.
  • OR, the current is limited to 1.3A

During compliance testing output is going to be overloaded (all the way down to a short) to see if requirements are met. (See Note)

Recommendation- limit current to telecom network to 1.3A.

Separation from earth

It is very important to separate the telecom network from the earth bonding in your product.

Recommendation- Any over-voltage protectors (Gas Arrestors or similar) which are connected to the earth bonding of the product shall have a minimum DC sparkover voltage of 1.6 times the rated voltage of the unit.

There are exclusions for separation from earth if voltage protectors have DC sparkover voltage of  less than 1.6 time of the voltage rating of the unit.

 Note: Standard allows additional testing options- Contact your testing lab or Ask the Expert


 

POTS lines, xDSL lines, ISDN U interface (TNV-3)

POTS (Plain Old Telephone System) refers to typical telephony lines for which there is always a DC remote power feeding voltage, audio signal is superimposed on the DC signal, ringing signals exist on the line for short periods of time.

xDSL lines are high frequency links that can reach very high data rate speeds for long distances. Typically a DC component is used for remote power feed. This voltage may be a few hundred volts.

ISDN U interface is typically connected to the central office unlike ISDN S interface which is typically considered a SELV interface.

DESIGN REQUIREMENTS

DESIGN GUIDE

Accessibility

No access to TNV3 connectors with the TEST PROBE 

No access to TNV3 circuits with TEST FINGER

Voltage limitations

Europe- 120Vdc and 70.7Vp. For voltages other than ringing voltages

US- 60Vdc and 42.4Vp. For voltages other than ringing voltages

Recommendations-

  • Ringing voltage must comply with one of the following
  • Europe and US: Current through 5Kohm shall be less than 20ma for continuos ringing
  • US only: 200Vp or 300Vpp voltage max over a 1Mohm
  • Other rules also apply for cadence ringing . Consult your safety lab for details or refer to annex M.2 and M.3 in IEC60950

Physical spacing 

Basic insulation required.

Recommendations -As a rule of thumb, design with insulation gap between telecom circuitry and SELV circuitry of 1.5mm

Electrical separation

TNV3 circuits Shall be separated from SELV  circuits by  1000Vac or 1414Vdc (sample diagram 1) (See Note)

TNV3 circuits Shall be separated from Mains  circuits by  2000Vac or 2828Vdc for US (sample diagram 2) (See Note)

TNV3 circuits Shall be separated from Mains  circuits by  3000Vac or 4242Vdc for Europe (sample diagram 2) (See Note)

UL over-voltage

Need to perform tests for overvoltage from line crossing

Protection of Telecommunication wiring from Over-heating

The following apply:

  • Connecting wires and cables AWG is clearly defined in installation instructions.
  • OR, the current is limited to 1.3A

During compliance testing output is going to be overloaded (all the way down to a short) to see if requirements are met. (See Note)

Recommendations- limit current to telecom network to 1.3A.

Separation from earth

It is very important to separate the telecom network from the earth bonding in your product.

Recommendations-

  • Any over-voltage protectors (Gas Arrestors or similar) which are connected to the earth bonding of the product shall have a minimum DC sparkover voltage of 1.6 times the rated voltage of the unit. There are exclusions for separation from earth if voltage protectors have DC sparkover voltage of  less than 1.6 time of the voltage rating of the unit. Consult your safety lab for details.
  • Some modern SLICs offer no separation from earth. They are typically supplied by DC directly to the SLIC. These SLICs comply with safety requirements only if DC voltage, supplied to the SLIC, which becomes ringing  voltage on the tip and ring is kept at SELV levels of 60Vdc or below.

Note: Standard allows additional testing options- Contact your testing lab or Ask the Expert


PBX telephone lines (TNV2)

PBX telephone lines are intrabuilding lines which are not exposed to overvoltages.

DESIGN REQUIREMENTS

DESIGN GUIDE

Accessibility

No access to TNV2 interface connectors with the TEST PROBE 

No access to TNV2 interface circuits with TEST FINGER

Voltage limitations

Europe- 120Vdc and 70.7Vp. For voltages other than ringing voltages

US- 60Vdc and 42.4Vp. For voltages other than ringing voltages

 

Physical spacing 

Basic insulation required.

Recommendations -As a rule of thumb, design with insulation gap between telecom circuitry and SELV circuitry of 1.5mm

Electrical separation

TNV2 interface circuits Shall be separated from SELV  circuits by  897Vac or 1268Vdc (sample diagram 1) (See Note)

TNV2 interface circuits Shall be separated from Mains  circuits by  2000Vac or 2828Vdc for US (sample diagram 2) (See Note)

TNV2 interface circuits Shall be separated from Mains  circuits by  3000Vac or 4242Vdc for Europe (sample diagram 2) (See Note)

UL over-voltage

Not Applicable

Protection of Telecommunication wiring from Over-heating

The following apply:

  • Connecting wires and cables AWG is clearly defined in installation instructions.
  • OR, the current is limited to 1.3A

During compliance testing output is going to be overloaded (all the way down to a short) to see if requirements are met. (See Note)

Recommendations- limit current to telecom network to 1.3A.

Separation from earth

It is very important to separate the telecom network from the earth bonding in your product.

Recommendations-

  • Any over-voltage protectors (Gas Arrestors or similar) which are connected to the earth bonding of the product shall have a minimum DC sparkover voltage of 1.6 times the rated voltage of the unit. There are exclusions for separation from earth if voltage protectors have DC sparkover voltage of  less than 1.6 time of the voltage rating of the unit. Consult your safety lab for details.

 

    Note: Standard allows additional testing options- Contact your testing lab or Ask the Expert


Sample Testing Diagrams

No 1

 

 

No 2

 

 

 


OVER-VOLTAGE PROTECTION FROM LINE CROSSING

NOTE- Over-voltage testing is conditioned by many variables. The following is the basic set of requirements only. It is highly recommended to consult your test lab at the beginning of your design.

In the US testing for overvoltage from line crossing is defined in UL 1950. It is mandatory to do this test for the US.

In Europe, the standards that apply to overvoltages from line crossing are ITU-T K20, K21. The application of these standards is not mandatory and depends on the specific requirements of the end user.

During over-voltage testing up to 24,000VA are placed on the tip and ring of the telecom interface. The results can be destructive.

During over voltage testing the following voltages are typically applied in common and metallic modes.

    • 600Vrms 40A for 1.5 seconds (with 2A fuse)
    • 600Vrms 7A for 5 seconds (no fuse used)
    • 600Vrms 2.2A for 30 minutes (no fuse used)

Many  vendors offer protection solutions. See following for components and  Application examples

Teccor: http://www.teccor.com

Raychem: http://www.raychem.com

Wickmann: http://www.wickmann.com

Littelfuse: http://www.littelfuse.com


Exclusions for separation from earth for telecom interfaces

The requirements of separation from earth do not apply to any of the following:

  • PERMANENTLY CONNECTED EQUIPMENT or PLUGGABLE EQUIPMENT TYPE B;
  • equipment that is intended to be installed by SERVICE PERSONNEL and has installation instructions that require the equipment to be connected to a socket-outlet with a protective earthing connection
  • equipment that has provision for a permanently connected PROTECTIVE EARTHING CONDUCTOR and is provided with instructions for the installation of that conductor.

NOTE – In Finland and Norway, the exclusions are applicable for PERMANENTLY CONNECTED EQUIPMENT and PLUGGABLE EQUIPMENT TYPE B only.

 

Subscribe to our newsletter:
Enter your
email address

subscribe
unsubscribe
 

Basics

Product Design

Telecoms Design Guide

IEC 60950

EMC Guidebook

 

  Disclaimer and Acknowledgment   

© i-Spec.com Ltd. 1999-2004. All rights reserved.

All extracts from the publication IEC 60950 have been reproduced by kind permission of the International Electrotechnical Commission (IEC). Copyright © IEC, Geneva, Switzerland.